Book a Demo

Sensedge Mini Technical Specifications

(SE-200 & SE-200P)

Particulate Matter Sensor

Sensor technology

Laser particle sensor (Light scattering)

Mass concentration accuracy for PM2.5

0 to 30 μg/m³:            ±3 μg/m³

30 to 1000 μg/m³:    ±10 % m.v.

Mass concentration range

0 to 1,000 μg/m³

Mass concentration size range

PM1: 0.3 to 1.0 μm

PM2.5: 0.3 to 2.5 μm

PM10: 0.3 to 10.0 μm

Sensor output resolution

1 μg/m³

Typical response time

≤10 s

Calibration

Calibrated against standardized aerosol mix

TVOC Sensor

Sensor technology

Multi-pixel metal oxide sensor (MOx)

Accuracy

±15 % ±8 ppb

Measurement range

0 - 60000 ppb

Sensor output resolution

1 ppb

Target gas profile

Complex mixture of 22 VOCs1 as defined by Molhave et al.

Sampling process

Diffusion

Calibration

Calibrated against ethanol

CO2 Sensor

Sensor technology

Non-dispersive infrared (NDIR)

Accuracy4

± 40 ppm ± 3%

Comply with ANSI/ASHRAE Standard 62.1-2022

Measurement range

400 to 2,000 ppm2

Up to 10,000 ppm extended range3

Sensor output resolution

1 ppm

Typical response time

2 minutes by 90 %

Ozone Sensor5

Sensor technology

Electrochemical

Accuracy

±10 %

Measurement range

20 to 2,000 ppb

Sensor output resolution

1 ppb

Typical response time

< 90 s

Interference gas

NO2, CL2, H2, CO

Temperature Sensor

Sensor technology

Digital sensor

Accuracy

±1 °C
Comply with WELL7

Measurement range

-40 - 125 °C

Sensor output resolution

0.01 °C

Typical response time6

>2 s

Relative Humidity Sensor

Sensor technology

Digital sensor

Accuracy

±5 % RH

Measurement range

0 - 100 % RH

Sensor output resolution

0.01 % RH

Typical response time8

>8 s

Power

Direct Wiring

12 - 30 V DC

USB-C

100-240V AC (5V 1.8A DC)

PoE (Available for model SE-200P)

IEEE 802.3af (PoE), Class3

IEEE 802.3at (PoE+), Class3

PD maximum power ≤ 10 W

PSEs: Midspan & endspan supported

Cable: Cat5 (Cat5e, Cat6, and Cat6a)9

Power consumption

Average: 1.7W

Peak: 4~5W

Connectivity

Wi-Fi

2.4 GHz 802.11 b/g/n

Security supported: 64/128 WEP,

WPA-PSK, WPA2-PSK, WPA, WPA2

Personal

Ethernet

IEEE 802.3

Data rate: Up to 100 Mbps

Communication

Cloud MQTT

On premise MQTT

Open API

Building Integrations

RS-485 Modbus/RTU

BACnet/IP

Data Storage & Logging

Frequency of readings
(Log interval)

1 minute, 1 hour, 1 day

Data push interval

 1 minute10

Onboard memory 

1 hour of data

Modules & Calibration

Compatible Modules

KM-200: Particulate Matter (PM2.5 & PM10) sensor module

KM-203: TVOC sensor module

KM-207: Ozone+TVOC sensor module

Calibration

Calibration via replaceable sensor modules

Security

Kaiterra’s platform architecture meets the most stringent security standards and is regularly subjected to 3rd party penetration tests. Read more about our security here.

Certifications

Environmental

ROHS, WEEE, TDRA, SRRC

Safety

FCC (US), CE (Europe), BIS (India)

Quality

RESET Grade B

Healthy Building

Works with WELL

Building Automation

BTL Certified under the BACnet Smart Sensor (B-SS) device profile

Size & Weight

Length

155 mm (6.1 in)

Height

34 mm (1.3 in)

Width

129 mm (5.1 in)

Weight

370 g (0.82 lbs)

Installation

Methods

Surface mount

Drywall mount

Electrical box mount

Recommended Monitor Placement

One monitor per 3,500ft² (325m²)

Space types and layouts should be considered in accordance with project requirements.

Operating Conditions

Operational temperature: 0 - 50 °C

Operational humidity: 5 to 95 %RH, non-condensing

Warranty

Standard warranty

1 year11

  1. n-Hexane, n-Nonane, n-Decane, n-Undecane ,1-Octane, 1-Decene, Cyclohexane, m-Xylene, Ethylbenzene, 1,2,4-Trimethylbenzene, n-Propylbenzene, a-Pinene, n-Pentanal, n-Hexanal, Iso-propanol, n-Butanol, 2-Butanone, 3-Methyl-3-butanone, 4-Methyl-2-pentanone, n-Butylacetate, Ethoxyethylacetate, 1, 2-Dichloroethane
  2. Extended exposure to concentrations below 400 ppm may result in incorrect operation of ABC algorithm and should be avoided.
  3. Sensor provides readings in the extended range but the accuracy may be lower than that specified in the table.
  4. The accuracy specification covers environments ranging from 0-50°C and 0-80% RH, and complies with indoor air quality standards ANSI/ASHRAE Standard 62.1-2022 at 25°C.
  5. Ozone measurement available with KM-207 module.
  6. Temperature response times strongly depend on the type of heat exchange, the surrounding surface and the airflow in the final application environment.
  7. As a RESET Certified Grade B air quality monitor, this device automatically meets technical requirements for this parameter.
  8. Humidity response times strongly depend on the surrounding surface and the airflow in the final application environment.
  9. Total length of cabling up to 100 meters.
  10. Customizable upon request.
  11. Optional extended warranty with contract.