Sensor technology
Laser particle sensor (Light scattering)
Mass concentration accuracy for PM2.5 1
0 to 30 μg/m³: ±3 μg/m³
30 to 1000 μg/m³: ±10 % m.v.
Mass concentration accuracy for PM10
0 to 30 μg/m³: ±3 μg/m³
30 to 1000 μg/m³: ±15 % m.v.
Mass concentration range
0 to 1,000 μg/m³
Mass concentration size range
PM1 0.3 to 1.0 μm
PM2.5 0.3 to 2.5 μm
PM10 0.3 to 10.0 μm
Sensor output resolution
1 μg/m³
Typical response time
≤10 s
Calibration
Calibrated against standardized aerosol mix
WELL specification requirements
Adjustable particle density (K-factor) to accommodate project/region specific particulate profile.
Complies with WELL Performance Verification Guidebook to be used in WELL certification.
Sensor technology
Non-dispersive infrared (NDIR)
Accuracy4
± 40 ppm ± 3%
Comply with ANSI/ASHRAE Standard 62.1-2022
Measurement range
400 to 2,000 ppm2
Up to 10,000 ppm extended range3
Sensor output resolution
1 ppm
Typical response time
2 minutes by 90 %
Sensor technology
Digital sensor
Accuracy
±1 °C
Certified by WELL6
Measurement range
-40 - 125 °C
Sensor output resolution
0.01 °C
Typical response time5
>2 s
Sensor technology
Digital sensor
Accuracy
±5 % RH
Measurement range
0 - 100 % RH
Sensor output resolution
0.01 % RH
Typical response time7
>8 s
Direct Wiring
12 - 30 V DC
Power supply
Input 90-305V AC
Output 24V DC, Frequency 47Hz to 63 Hz
PoE
(Available for model SE-201P)
IEEE 802.3af (PoE), Class3
IEEE 802.3at (PoE+), Class3
PD maximum power ≤ 10 W
PSEs: Midspan & endspan supported
Cable: Cat5 (Cat5e, Cat6, and Cat6a)8
Wi-Fi
2.4 GHz 802.11 b/g/n
Security supported: 64/128 WEP,
WPA-PSK, WPA2-PSK, WPA, WPA2
Personal
Ethernet
IEEE 802.3
Data rate: Up to 100 Mbps
Communication
Cloud MQTT
On premise MQTT
Open API
RS-485 Modbus/RTU
BACnet/IP
Frequency of readings
(Log interval)
1 minute, 1 hour, 1 day
Data push interval
1 minute9
Onboard memory
1 hour of data
Compatible Modules
KM-200: Particulate Matter (PM2.5 & PM10) sensor module
Calibration
Calibration via replaceable sensor modules
Kaiterra’s platform architecture meets the most stringent security standards and is regularly subjected to 3rd party penetration tests. Read more about our security here.
Environmental
ROHS, WEEE, TDRA, SRRC
Safety
FCC (US), CE (Europe), BIS (India)
Quality
RESET Grade B
Healthy Building
Works with WELL
Building Automation
BTL Certified under the BACnet Smart Sensor (B-SS) device profile
Length
190 mm (7.5 in)
Height
170 mm (6.7 in)
Width
80 mm (3.2 in)
Weight
Sensedge Mini: 370 g (0.82 lbs)
Outdoor housing: 426 g (0.94 lbs)
Surface mount
Electrical box mount
Operational temperature: -20 - 50 °C
Operational humidity: 5 to 95 %RH, non-condensing
Standard warranty
1 year10
- Operates with high accuracy and reliability down to temperatures of -20°C. Performance may degrade below -20°C
- Extended exposure to concentrations below 400 ppm may result in incorrect operation of ABC algorithm and should be avoided.
- Sensor provides readings in the extended range but the accuracy may be lower than that specified in the table.
- The accuracy specification covers environments ranging from 0-50°C and 0-80% RH, and complies with indoor air quality standards ANSI/ASHRAE Standard 62.1-2022 at 25°C.
- Temperature response times strongly depend on the type of heat exchange, the surrounding surface and the airflow in the final application environment.
- As a RESET Certified Grade B air quality monitor, this device automatically meets technical requirements for this parameter.
- Humidity response times strongly depend on the surrounding surface and the airflow in the final application environment.
- Total length of cabling up to 100 meters. However, we don’t recommend using cables longer than 50m to guarantee the stability of power and data transmission.
- Customizable upon request.
- Optional extended warranty with contract.